InteliMains 210 Global Guide
530
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left phase voltage in phases 1. The following
setpoints are related to it:
Bus Left Overvoltage (page 188)
Bus Left < > Voltage Delay (page 189)
6 back to List of alarms level 2
Alarm Type Breaker open
Alarmlist message No
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left phase voltage in phases 1. The following
setpoints are related to it:
Bus Left Overvoltage (page 188)
Bus Left < > Voltage Delay (page 189)
Bus Left L1 Overvoltage
6 back to List of alarms level 2
Alarm Type Breaker open
Alarmlist message No
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left voltage unbalance. The following setpoints are
related to it:
Bus Left Voltage Unbalance (page 189)
Bus Left Voltage Unbalance Delay (page 189)
Bus Left Voltage Unbalance
6 back to List of alarms level 2