InteliMains 210 Global Guide
188
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units]
1 .. 200 [%] of Nominal Current (page 175)
Default value 50 % Alternative config NO
Step
1 % of Nominal Current (page 175)
Comm object 8284 Related applications MCB, MGCB, BTB
Description
Threshold for Bus Left current asymmetry (unbalance).
Current Unbalance
6 back to List of setpoints
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units] 0,0 .. 600,0 [s]
Default value 5,0 s Alternative config NO
Step 0,1 s
Comm object 8285 Related applications MCB, MGCB, BTB
Description
Delay for Current Unbalance (page 188) protection.
Current Unbalance Delay
6 back to List of setpoints
Subgroup: Bus Left Voltage Limits
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units]
Bus Left Undervoltage (page 188) .. 150 [%]
Default value 110 % Alternative config NO
Step
1 % of Nominal Voltage Ph-Ph (page 177)
Comm object 8305 Related applications MCB, MGCB, BTB
Description
Threshold for Bus Left overvoltage. All three phases are checked. Maximum out of three is used.
Bus Left Overvoltage
6 back to List of setpoints
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units]
50 .. Bus Left Overvoltage (page 188) [%]
Default value 60 % Alternative config YES
Step
1 % of Nominal Voltage Ph-Ph (page 177)
Comm object 8307 Related applications MCB, MGCB, BTB
Description
Threshold for Bus Left undervoltage. All three phases are checked. Minimum voltage out of three phases is
used.
Bus Left Undervoltage
6 back to List of setpoints