InteliMains 210 Global Guide
189
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units] 0,0 .. 600,0 [s]
Default value 2,0 s Alternative config YES
Step 0,1 s
Comm object 8306 Related applications MCB, MGCB, BTB
Description
Delay for Bus Left Undervoltage (page 188) and Bus Left Overvoltage (page 188) protection.
Bus Left < > Voltage Delay
6 back to List of setpoints
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units]
1 .. 150 [%] of Nominal Voltage Ph-Ph (page 177)
Default value 10 % Alternative config NO
Step
1 % of Nominal Voltage Ph-Ph (page 177)
Comm object 8446 Related applications MCB, MGCB, BTB
Description
Threshold for Bus Left voltage unbalance.
Bus Left Voltage Unbalance
6 back to List of setpoints
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units] 0,0 .. 60,0 [s]
Default value 2,0 s Alternative config NO
Step 0,1 s
Comm object 8447 Related applications MCB, MGCB, BTB
Description
Delay for Bus Left Voltage Unbalance (page 189) protection.
Bus Left Voltage Unbalance Delay
6 back to List of setpoints
Subgroup: Bus Left Frequency Limits
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units]
Bus Left Underfrequency (page 190) .. 150 [%]
Default value 102,0 % Alternative config NO
Step
1,0 % of Nominal Frequency (page 178)
Comm object 8310 Related applications MCB, MGCB, BTB
Description
Threshold for Bus Left overfrequency.
Bus Left Overfrequency
6 back to List of setpoints