EasyManuals Logo

ComAp InteliMains 210 BTB User Manual

ComAp InteliMains 210 BTB
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #190 background imageLoading...
Page #190 background image
InteliMains 210 Global Guide
190
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units]
50 .. Bus Left Overfrequency (page 189) [%]
Default value 98,0 % Alternative config NO
Step
1,0 % of Nominal Frequency (page 178)
Comm object 8312 Related applications MCB, MGCB, BTB
Description
Threshold for Bus Left underfrequency.
Bus Left Underfrequency
6 back to List of setpoints
Setpoint group Bus Left Settings Related FW 2.0.0
Range [units] 0,0 .. 600,0 [s]
Default value 0,5 s Alternative config NO
Step 0,1 s
Comm object 8311 Related applications MCB, MGCB, BTB
Description
Delay for Bus Left Underfrequency (page 190) and Bus Left Overfrequency (page 189) protection.
Bus Left < > Frequency Delay
6 back to List of setpoints