InteliMains 210 Global Guide
529
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left phase voltage in phases. The following setpoints
are related to it:
Bus Left Undervoltage (page 188)
Bus Left < > Voltage Delay (page 189)
Note: Alarm is active only in case the setpoint Connection type (page 176) is
set to 3Ph4Wire.
6 back to List of alarms level 2
Alarm Type Breaker open
Alarmlist message No
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left voltage between phases L3 a L1. The following
setpoints are related to it:
Bus Left Overvoltage (page 188)
Bus Left < > Voltage Delay (page 189)
Note: Alarm is active only in case the setpoint Connection type (page 176) is
set to 3Ph3Wire or High Leg D or SplitPhase.
Bus Left L3L1 Overvoltage
6 back to List of alarms level 2
Alarm Type Breaker open
Alarmlist message No
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left voltage between phases L3 a L1. The following
setpoints are related to it:
Bus Left Undervoltage (page 188)
Bus Left < > Voltage Delay (page 189)
Note: Alarm is active only in case the setpoint Connection type (page 176) is
set to 3Ph3Wire or High Leg D or SplitPhase.
Bus Left L3L1 Undervoltage
6 back to List of alarms level 2
Alarm Type Breaker open
Alarmlist message No
Alarm evaluated All the time
Bus Left L1 Overvoltage