EasyManua.ls Logo

Condair UDC - Wiring Diagrams;Configuration

Condair UDC
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41Condair CRC and CRC-NA
3.7 Wiring diagrams/Conguration
3.7.2.1 Wiring diagram/Conguration Condair CRC
24V AC/DC
1
0V / GND
2
H OUT
3
STATUS
LED
JP1 JP3
RH OUT
0V / GND
24 V AC/DC ±10%
JP1 Signal type
3
2
1
U1
0-10V, 2-10V
3
2
1
I1
0-20mA, 4-20mA
JP3 Signal range
3
2
1
U1: 0-10V
I1: 0-20mA
3
2
1
U1: 2-10V
I1: 4-20mA
Status LED
No light: no power
5 s blinking: Normal
1 s blinking: Sensor element defective
3.7.2.2 Wiring diagram Condair CRC-NA
GND / 0V
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
24V
N/A
N/A
N/A
AO 2-10V
N/A
Temp. Reset
RH OUT
24 V AC/DC ±10%