84 Condair CHD, CHD-S and CHD-NA
6.4 Mounting location
Mount the Condair CHD in the supply air duct at least 3 meters downstream from the nearest fan and
coil and with a minimum distance of 5x the humidication distance to the steam distributor (see manual
of the humidier).
6.5 Installation
1. At the place of location drill a hole with a diameter of 16 mm (5/8") as well as 4 holes for the self
tapping screws into the duct.
2. Open the screw on the housing cover and remove cover.
3. Lead connecting cable through the cable gland and connect wires to the terminals according to the
wiring diagram.
4. Attach gasket to the sensor side of the housing (self-adhesive).
5. Insert the probe into the hole in the duct, then x housing to the duct using the 4 self-tapping screws
provided.
6. Snap cover into the hinge of the housing, then close cover and x it with the screw (do not tighten
screw too much).