7Condair UDC
1.4 Mounting location
The Condair UDC is installed directly on the duct.
– Mounting in the extract air duct (recommended):
Mount the UDC in the extract air duct close to the air outlet of the room but downstream from a
extract air fan if one is present.
– Mounting in the supply air duct:
Mount the UDC in the supply air duct at least 3 meters downstream from the nearest fan and coil
and with a minimum distance of 5x the humidication distance to the steam distributor (see manual
of the humidier).
1.5 Installation
1. At the place of location drill a hole with a diameter of 16 mm (5/8") into the duct (see dimensional
drawing).
2. Stick the supplied self-adhesive gasket concentrically over the hole in the duct and attach the duct
ange to the ventilation duct using the self-tapping screws supplied.
3. Insert the probe of the universal controller through the duct ange into the duct and secure it with
the lock nut.
4. Loosen the screw on the housing cover and open the cover.
5. Lead connecting cable through the cable gland into the controller and connect wires to the terminals
according to the wiring diagram.
6. Close cover and x it with the screw (do not tighten screw too much).