70 Condair RCC and RCC-NA
5.6 Product specications
5.6.1 Technical data
Power Supply
Operating voltage 24 V AC 50/60 Hz ± 10%, 24VDC ± 10%
Power consumption Max. 3 VA
Terminal connections For wires 0.34…2.5 mm
2
(AWG 24…12)
Sensor probe
Measuring element Capacitive measuring element
Measuring range 0…100 %rH
Measuring accuracy
100
0
±1
±2
±3
±4
±5
%rF
%rh
%hr
%rF
%rh
%hr
20 30 40 50 60 70 80 90 100
Max. rH tolerance at 25 °C (77°F)
Hysteresis ± 1%
Repeatability ± 0.1%
Stability < 0.5% / year
Signal inputs
Universal inputs UI1, UI2
Signal outputs
Analog output AO1
Analog signal 0...10 VDC or 0…20mA
Resolution 39 mV or 0.078 mA
Maximum load 10 mA (at 0...10 VDC) 20 mA (at 0…20mA)
Environment
Operation IEC 721-3-3
Climatic Conditions Class 3 K5
Temperature 0…50 °C (32…122 °F)
Humidity <95 %rH not condensing
Transport and Storage IEC 721-3-2 and IEC 721-3-1
Climatic Conditions Class 3 K3 and Class 1 K3
Temperature -25…70 °C (-13…158 °F)
Humidity <95 %rH not condensing
Mechanical Conditions Class 2M2
Standards
CE compliant to EMC Norm 2014/30/EU, Low
Voltage Directive 2014/35/EU
EN 61 000-6-1/ EN 61 000-6-3
Automatic electrical control and regulating de-
vices for domestic use and similar applications
EN 60 730 –1
Degree of protection according to 60529 IP30
Protection class III (IEC 60536)
General
Housing material ABS
Mounting plate Galvanized steel
Weight (including packaging) 260 g (9.2 oz)