BEC62(08) technical manual
10
Product specifications
Voltage ratings (per phase)
Nominal voltage (-20% +15%)
110 - 127 V AC 220 - 240 V AC
Supply frequency (±5%)
60Hz 50Hz
Current ratings
Base current (I
b
)
10A 10A
Maximum current (I
max
)
100 A 100A
Minimum starting current
Class 1
Class 2
40mA 40mA
50mA 50mA
Utilisation category
UC2 UC2
Nominal power consumption
1.6 W / 9 VA 1.6 W / 9 VA
Accuracy
Class 1 or 2
(maintained throughout life of product)
Over voltage rating
1.8 times the nominal voltage for 48 hours
Short circuit rating
Short-circuit withstand 3.0 kA
Protection
Power overload Thermal overload
Current overload Galvanic isolation
Over/under voltage Tamper protection
Phase imbalance
Environmental
Operating temperature
-10°C to +55°C
Storage temperature
-25°C to +70°C
Humidity
95% non-condensing
IP rating
IP 54
RF immunity
30 V/m
Status indicators
Power / load status LED
Rate LED (1,000 pulses / kWh)
Communication status LED