EasyManua.ls Logo

Conlog BEC62 - Troubleshooting and Error Handling; Supply Disconnection and Reasons

Conlog BEC62
59 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41
BEC62(08) technical manual
Troubleshooting
Disconnection of supply
Automatic disconnection
The BEC62(08) meter automatically disconnects the consumer's supply in the event of a trip. The
meter supports the following individual trip events, that are registered and saved when the meter trips.
Trip event type
Reconnection type
Tamper
Automatic reconnection by entering a clear tamper token
Thermal overload
Automatic reconnection
Current overload
Automatic reconnection
Power overload
Automatic reconnection
Under voltage
Automatic reconnection
Over voltage
Automatic reconnection
Unbalanced power
overload
Automatic reconnection
If more than one trip event is detected, only the trip event with the highest priority is recorded.
You can view the reason for the last, highest priority disconnection, using the short code #073#.

Table of Contents

Related product manuals