BEC62(08) technical manual
STS token result
Short code: #078#
The display indicates a value of 13, which is a CRC error
The STS token result indicates the status of the previous STS token entered into the meter. The result
is stored in the token status register. An extract of the status register values is displayed below.
Value
Description of error
0
Reserved for future assignment
1
Accept: The token is accepted
2
1stKCT: The first key change token has been entered
3
2ndKCT: The second key change token has been entered
4
Overflow Error: Acceptance of the token would cause an overflow of register in the
meter.
5
Key type error: Indicates that the decoder key is possibly being changed from one key
type to another which is in violation of the key change rules
6
Format error: The format of the token does not comply with the required format
7
Range error: The range of the data is outside of the defined range of values
8
Function error: The function has not been implemented/is not supported by the meter
application process
9
Old error: Token is expired
10
Used error: Token has already been used (duplicate)
11
Key expired error: Meter key has expired
12
DDTK error: a transfer credit token may not be processed using a default key type
13
CRC error: The data contained in the token cannot be verified and may be corrupted
14
Mfr code error: The manufacturer value in the Class 1 token does not match the
manufacturer code value for the decoder
15
Token lockout status: Token lockout is active
16
Token status not ready: The processing of the last token entered via a virtual carrier
has not been completed
17-255
Reserved for future assignment