99
Parameter Name
LCD Display
Description
IEEE1547 Rule21 ISO-NE
Min Default
Max Min Default
Max Min Default
Max
OvrFrqDeratingM
ode
Over frequency
derating
enable/disable
0: Disable
1: Enable
0 0 1 0 0 1 0 0 1
CtrMode
active power
0: Disable dispatch
1: Remote dispatch
2: Local control
0 0 2 0 0 2 0 0 2
Percentage
Local electric
dispatch Active
Power setting value
0 100 100 0 100 100 0 100 100
6.2.6 Reactive Power Derating Setup
The Reactive Power Derating menu is used to set the Grid reactive power
derating parameters including PF parameters, Qu parameters, etc. The
parameters as shown in Table 6-8.
PF vs Grid Voltage
PFCurveP1
P1/4
PFpCurvePF1
100.0%
1.000
50.0%
PFpCurvePF2
PFCurveP2
PFCurveTriVolt
PFCurveUndoVolt
-0.900
100.00%
90.00%
QuCurveQ2i
P3/4
5.0%
20.0%
50.0%
QuCurveTriPower
QuCurveUndoPower
Reactive Power vs Grid Voltage
Grid Reactive Power Derating
P4/4
CtrMode
0
Percentage
0.0%
Reactive Power vs Grid Voltage
QuCurveQ1
QuCurveU1
P2/4
-50.0%
110.00%
0.0%
107.99%
92.01%
0.0%
90.00%
QuCurveU2
QuCurveQ2
QuCurveU1i
QuCurveQ1i
QuCurveU2i
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
PFSetValue
1.000
Reserve
Figure 6-14 Reactive Derating Setting