105
Table 6-11 Other Parameters
Other Parameters Setting Range
Parameter
Name
Description IEEE1547 Rule21 ISO-NE
Min Default Max Min Default Max Min
Default
Max
PowerOnDelay
(s)
Startup delay time
0 5 1200 0 5 1200 0 5 1200
ReactivePower
Step
%
Reactive Step 0.0 25.0 100.0 0.0 25.0 100.0 0.0 25.0 100.0
ErrSoftStartP
(%/P)
Power startup step
after Grid Fault
0.01 0.16 10 0.01 2 10 0.01 0.16 10
NormSoftStopP
(%/P)
Normal power step
in soft stop
0.01 6 100 0.01 10 100 0.01 10 100
NormSoftStartP
(%/P)
Normal power step
in soft startup
0.01 4 100 0.01 100 100 0.01 2 100
NormalDerating
Step
Power step in
Derarting
0.01 6 100 0.01 100 100 0.01 6 100
PVSlowStartSt
ep
%
PVSlowStartStep 0.01 10.00 100.00 0.01 10.00 100.00
0.01 10.00 100.00
PVSlowStartPw
Delta%
The output power
should be slow
increased due to
the change of PV
illumination at the
Rule21 standard.
5.00 5.00 10.00 5.00 5.00 10.00 5.00 5.00 10.00
FaultPowerT
The trigger
temperature of
module (C)
95 95 95 95 95 95 95 95 95
FaultEnvT
The trigger
temperature of
enviroment (C)
83 83 83 83 83 83 83 83 83
GFCIStaticValu
e (mA)
The static
threshold value of
Leakage current
100 650 1000 100 650 1000 100 250 1000
GFCIStaticT (s)
The static
threshold time of
Leakage current
0 0.20 655 0 0.20 655 0 0.20 655

Table of Contents