105
Table 6-11 Other Parameters
Other Parameters Setting Range
Parameter
Name
Description IEEE1547 Rule21 ISO-NE
Min Default Max Min Default Max Min
Max
PowerOnDelay
Startup delay time
0 5 1200 0 5 1200 0 5 1200
ReactivePower
(
)
Reactive Step 0.0 25.0 100.0 0.0 25.0 100.0 0.0 25.0 100.0
ErrSoftStartP
Power startup step
after Grid Fault
0.01 0.16 10 0.01 2 10 0.01 0.16 10
NormSoftStopP
Normal power step
in soft stop
0.01 6 100 0.01 10 100 0.01 10 100
NormSoftStartP
Normal power step
in soft startup
0.01 4 100 0.01 100 100 0.01 2 100
NormalDerating
Power step in
0.01 6 100 0.01 100 100 0.01 6 100
PVSlowStartSt
(
)
PVSlowStartStep 0.01 10.00 100.00 0.01 10.00 100.00
0.01 10.00 100.00
PVSlowStartPw
Delta(%)
The output power
should be slow
increased due to
the change of PV
illumination at the
5.00 5.00 10.00 5.00 5.00 10.00 5.00 5.00 10.00
FaultPowerT
The trigger
temperature of
95 95 95 95 95 95 95 95 95
FaultEnvT
The trigger
temperature of
83 83 83 83 83 83 83 83 83
GFCIStaticValu
e (mA)
The static
threshold value of
Leakage current
100 650 1000 100 650 1000 100 250 1000
GFCIStaticT (s)
The static
threshold time of
0 0.20 655 0 0.20 655 0 0.20 655