Other Parameters Setting Range
Parameter
Name
Description IEEE1547 Rule21 ISO-NE
Min Default Max Min Default Max Min
Max
GFCIDynProFa
ctor
The dynamic
trigger coefficient
0 100 200 0 100 200 0 100 200
DCIProtection1
Maximum DCI
0.01 2.50 5 0.01 2.50 5 0.01 0.50 5
DCIProtectionT
Trip time 1 of DCI
0 10 120 0 10 120 0 60 120
DCIProtection2
Maximum DCI
5 950 5000 5 950 5000 5 950 5000
DCIProtectionT2
Trip time 2 of DCI 0 1 120 0 1 120 0 1 120
PVStartVolt(V)
-
300 330 400 300 330 400 300 330 400
MPPTScanPeri
MPPT Scan Cycle
300 3600 5400 300 3699 5400 300 3600 5400
ISOProtection
(Ω)
Minimum
insulation
1k 100k 2000k 1k 100k 2000k 1k 100K 2000k
StarUPMinTem
p (C)
The minimum
startup
-35 -30 -20 -35 -30 -20 -35 -30 -20
DuplicationGro
Parameter of
0 30 100 0 30 100 0 0 100
CtrParaGroup
The enabled
control parameters
group.
0 4 4 0 4 4 0 4 4