106
Other Parameters Setting Range
Parameter
Name
Description IEEE1547 Rule21 ISO-NE
Min Default Max Min Default Max Min
Default
Max
GFCIDynProFa
ctor
The dynamic
trigger coefficient
of Leakage current
0 100 200 0 100 200 0 100 200
DCIProtection1
Maximum DCI
value1
0.01 2.50 5 0.01 2.50 5 0.01 0.50 5
DCIProtectionT
1 (s)
Trip time 1 of DCI
0 10 120 0 10 120 0 60 120
DCIProtection2
(mA)
Maximum DCI
value2
5 950 5000 5 950 5000 5 950 5000
DCIProtectionT2
(s)
Trip time 2 of DCI 0 1 120 0 1 120 0 1 120
PVStartVolt(V)
PV start
-
up voltage
300 330 400 300 330 400 300 330 400
MPPTScanPeri
od (s)
MPPT Scan Cycle
300 3600 5400 300 3699 5400 300 3600 5400
ISOProtection
(Ω)
Minimum
insulation
resistance
1k 100k 2000k 1k 100k 2000k 1k 100K 2000k
StarUPMinTem
p (C)
The minimum
startup
temperature
-35 -30 -20 -35 -30 -20 -35 -30 -20
DuplicationGro
up
Parameter of
repetitive control
0 30 100 0 30 100 0 0 100
CtrParaGroup
The enabled
control parameters
group.
0 4 4 0 4 4 0 4 4