10 | Configuration
Installer reference guide
187
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
# Code Description
[9.6.2] [5‑03] Priority temperature: Used for
calculation of anti-recycling timer. If [5‑02]=1, it
defines the outdoor temperature below which
the backup heater will assist during domestic
hot water heating.
[5‑01] Equilibrium temperature and [5‑03]
Space heating priority temperature are related
to backup heater. So, you must set [5‑03] equal
or a few degrees higher than [5‑01].
Timers for simultaneous space and domestic hot water operation request
[8-02]: Anti-recycle timer
t
1
0
1
0
[8-01] [8-02]
1 Heat pump domestic water heating mode (1=active, 0=not active)
2 Hot water request for heat pump (1=request, 0=no request)
t Time
[8-04]: Additional timer at [4-02]/[F-01]
t
T
A
t
T
A
0
[8-01]
[5-03] [4-02]
[8-02]
[8-01]+
[8-04]
0
[8-01]
[F-01] 35°C
[8-02]
[8-01]+
[8-04]
T
A
Ambient (outdoor) temperature
t Time
Anti-recycle timer
Maximum running time domestic hot water
# Code Description
[9.6.4] [8-02] Anti-recycle timer: Minimum time
between two cycles for domestic hot water. The
actual anti-recycling time also depends on setting
[8-04].
Range: 0~10 hours
Remark: The minimum time is 0.5 hours even
when the selected value is 0.
[9.6.5] [8-00] Minimum running timer:
Do NOT change.