10 | Configuration
Installer reference guide
188
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
# Code Description
[9.6.6] [8-01] Maximum running timer for domestic hot
water operation. Domestic hot water heating
stops even when the target domestic hot water
temperature is NOT reached. The actual
maximum running time also depends on setting
[8-04].
▪ When Control=Room thermostat: This
preset value is only taken into account if there
is a request for space heating or cooling. If
there is NO request for space heating/cooling,
the tank is heated until the setpoint has been
reached.
▪ When Control≠Room thermostat: This
preset value is always taken into account.
Range: 5~95 minutes
Remark: It is NOT allowed to set [8‑01] to a value
below 10 minutes.
[9.6.7] [8-04] Additional timer: Additional running time
for the maximum running time depending on the
outdoor temperature [4-02] or [F-01].
Range: 0~95 minutes
Water pipe freeze prevention
Only relevant for installations with water piping outdoors. This function tries to
protect outdoor water piping from freezing.
# Code Description
[9.7] [4-04] Water pipe freeze prevention:
▪ 1: Off (read only)
Preferential kWh rate power supply
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals
(X5M/9+10) as the safety thermostat. Thus, the system can have EITHER preferential
kWh rate power supply OR a safety thermostat.