8 | Electrical installation
Installer reference guide
85
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
▪ demand that the equipment only consumes a limited amount of electricity during
certain periods of time.
The indoor unit is designed to receive an input signal by which the unit switches
into forced off mode. At that moment, the unit compressor will not operate.
The wiring to the unit is different depending on whether the power supply is
interrupted or not.
Detail C1: Factory-mounted power supply cable
Wires: 3N+GND, OR 1N+GND
Maximum running current: Refer to name plate on unit.
Connect the factory-mounted power supply cable to a 1N~ or 3N~ power supply.
a
b
Q1DI
L1 L2 L3 N
3N~, 50 Hz, 400 V AC
F1B
1 3 5 7
2 4 6 8
IIII
Q1DI
L N
1N~, 50 Hz, 230 V AC
F1B
1 3 5 7
2 4 6 8
IIII
1N~ 3N~
OR
BRN
BLK
GRY
BLU
YLW/GRN
BRN
BLK
GRY
BLU
YLW/GRN
a Factory-mounted power supply cable
b Field wiring
F1B Overcurrent fuse (field supply). Recommended fuse for 1N~: 4‑pole, 32 A fuse, C
curve. Recommended fuse for 3N~: 4‑pole, 16A fuse, C curve.
Q1DI Earth leakage circuit breaker (field supply)
Detail C2: Preferential kWh rate power supply contact
Wires: 2×(0.75~1.25mm²)
Maximum length: 50m.
Preferential kWh rate power supply contact: 16VDC detection (voltage
supplied by PCB). The voltage-free contact shall ensure the minimum
applicable load of 15VDC, 10mA.
Connect the preferential kWh rate power supply contact (S1S) as follows.