8 | Electrical installation
Installer reference guide
86
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
X5M
9
10
S1S
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals
(X5M/9+10) as the safety thermostat. Thus, the system can have EITHER preferential
kWh rate power supply OR a safety thermostat.
Detail C3: Separate normal kWh rate power supply
Wires: 1N+GND
Maximum running current: 6.3A
Connect the separate normal kWh rate power supply as follows: