EasyManua.ls Logo

Daikin DZ17VSA481AA - Troubleshooting Operational Issues

Daikin DZ17VSA481AA
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2828
trouBleShootIng
ClimateTalk
Fault Code
PCB LED
Display
Transmitted ClimateTalk
Message
Thermostat Fault Probable Causes Corrective Actions
43 E43 HIGH LINE VOLT
Control detects a high power supply
voltage condition.
High line voltage supply
Verify unit is connected to power supply as specied on
rating plate
Correct high line voltage condition; Contact local utility if
needed
44 E44 OP TEMP RANGE
The control detects the outdoor
temperature outside recommended
operational range. Unit may continue
to operate normally.
Ambient air conditions too high or low
Cycle power; re-try during usable ambient temperature
range
45 E45 NO COOLING TEST
The control is unable to start the
Cooling mode test because indoor
heat has been turned on by ther-
mostat. Please set thermostat to off
position.
Heat provided by secondary heating
source
Turn off Furnace or heater using thermostat before
operation
47 E47 NO SYS VER TEST
The control is unable to start the
System Verication test because
indoor heat has been turned on by
thermostat. Please set thermostat to
off position.
Heat provided by secondary heating
source
Turn off Furnace or heater using thermostat before
operation
49 E49 NO CHARGE MODE
The control is unable to enter
Charging Mode because indoor heat
has been turned on by thermostat.
Please set thermostat to off position.
Heat provided by secondary heating
source
Turn off heater using thermostat before operation
50 E50 LINE VOLT CTRL
This indicates there is a voltage
issue on the control board. See
service manual for troubleshooting
information.
High or low voltage from supply voltage or
frequency
Faulty control board
Noise
Correct low/high line voltage condition; Contact local utility
if needed
Replace control board if necessary
Contact local utility if needed
51 E51 OD COMM ERROR
This indicates potential communica-
tion issues have been detected by
the outdoor control board.
Communication wiring disconnected Check communication wiring; Repair as needed
52 - COMP FAIL MINOR
This error indicates the equipment is
experiencing frequent compres-
sor faults. Control has determined
continued operation is acceptable.
This indicates they may be a problem
with the equipment.
Stop valve not completely open
The compressor wire is lost phase
Compressor motor failure
Check the opening of stop valve, should be full open;
Repair/replace if needed
Check the wire between control board and compressor
Inspect compressor motor for proper function; Replace if
necessary
53 - PCB OR FAN MIN
This error indicates the equipment is
experiencing frequent outdoor control
board and/or motor faults. Control
has determined continued operation
is acceptable. This indicates they
may be a problem with the equip-
ment.
Obstruction in fan rotation
Outdoor fan motor not connected properly
Outdoor fan not running
Faulty control board
Noise
Check and clean grille of any debris
Check wiring from Outdoor fan motor to control board;
Repair if needed
Check outdoor fan motor & wiring; Repair/replace if
needed
Replace control board if necessary
54 - EEV MINOR
This error indicates the equipment is
experiencing frequent low discharge
superheat faults.
Control has determined continued
operation is acceptable. This indi-
cates they may be a problem with the
equipment.
Thermistors inoperable or improperly
connected
Faulty indoor EEV or indoor EEV coil
Faulty control board
Check the connection to thermistors; Repair/replace if
needed
Check indoor EEV; Replace if needed
Check indoor EEV coil; Replace if needed
Replace control board if necessary
55 - HI DIS TEMP MIN
This error indicates the equipment is
experiencing frequent high discharge
temperature faults. Control has
determined continued operation is
acceptable. This indicates they may
be a problem with the equipment.
Discharge thermistor inoperable or improp-
erly connected
Discharge thermistor is put in incorrect
position or off
Low refrigerant charge
Overcharge
Faulty compressor
Check discharge thermistor resistance and connections;
Repair/replace as needed
Check discharge thermistor position
Check refrigerant charge level; Adjust if needed
Check the compressor; Repair/replace if needed
56 E56 SUCT TEMP FAIL
The control has detected if the
Outdoor Suction Temperature Sensor
is out of range.
Suction thermistor inoperable or not prop-
erly connected
Faulty reversing valve
Check the connection to suction thermistor; Repair/re-
place if needed
Check reversing valve; Replace if needed
57 - CL LOOP SWEAT
This indicates the control is sensing
sweating on the cooling loop.
<3.5 - 5.0 ton only>
Refrigerant Leak
Low refrigerant charge
Faulty indoor EEV or indoor EEV coil
Thermistors inoperable or improperly
connection
Test for system leaks using leak test procedure
Check refrigerant charge level; Adjust if needed
Check indoor EEV; Replace if needed
Check indoor EEV coil; Replace if needed
Check the connection to thermistors; Repair/replace if
needed
58 E58 OL OPEN
The Overload Protection sensor for
Compressor is opened.
Overload protection (OL) sensor inoper-
able
Check resistance on OL sensor to verify operation;
Replace if needed.
Check OL sensor position on compressor body.
59 E59 RV FAIL
This indicates the equipment is expe-
riencing reversing valve faults.
Faulty reversing valve body or coil
Low refrigerant charge
Faulty pressure sensor
Faulty control board
Check reversing valve body or coil; Replace if needed
Check refrigerant charge level; Adjust if needed
Check pressure sensor; Replace if needed
Replace control board if necessary
60 E60
NO HP HEAT
(WARM UP)
No heat pump heating.
Need warming up on compressor to
run properly.
Need 2 hour power ON.
Need heat up on compressor motor/oil.
Wait for 2 hours after turn-on power on Outdoor unit.
Use secondary heat source.
B0 Eb0 NO ID AIRFLOW
The estimated airow from indoor
subsystem is near to 0 CFM.
Failed indoor blower motor
Indoor fan motor not properly connected
Too much static pressure
Check ID fan motor wiring and connectors; Repair/replace
if needed
Check ID fan motor; Replace if needed
Check the obstruction inside duct work.

Table of Contents

Related product manuals