Daikin VRV K - 2.25 Outdoor Unit: Malfunction of Oil Temperature Thermistor (R5 T)

Daikin VRV K
170 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Si-95 Troubleshooting
Troubleshooting Inverter K Series 91
2.15 Outdoor Unit: Actuation of High Pressure Switch
Remote Controller
Display
EE
EE
33
33
Supposed Causes Actuation of outdoor unit high pressure switch
Defect of outdoor unit PC board (A1P)
Instantaneous power failure
Troubleshooting
1: Actuation of high pressure switch (HPS)
The outdoor unit PC boards connector is disconnected.
Is the outdoor unit heat exchanger dirty?
Defect of outdoor fan
Is the refrigerant over-charged?
Operation
is normal when turned on
again by remote
controller.
Replace outdoor unit PC board A1P.
Actuation of high pressure switch 1
YES
YES
There was an instantaneous power
failure or a past safety device actuated.
Re-check refrigerant system.
NO
NO
(VF041)
Contact
S1HP (X10A) or S2HP
(X11A) is open.
SI-95.BOOK Page 91 Friday, March 31, 2000 10:59 AM