Troubleshooting (Inverter) Si-95
122 Troubleshooting Inverter K Series
4.8 Outdoor Unit: Inverter Over-Ripple Protection
Remote Controller
Display
PP
PP
44
44
Supposed Causes Defect of radiator fin temperature sensor
Defect of inverter unit
Troubleshooting
(VF070)
Replace the radiator fin thermistor.
Turn on
again after letting 30
minutes or more pass after
occurrence of
malfunction.
"P4" occurs again.
SI-95.BOOK Page 122 Friday, March 31, 2000 10:59 AM