Daikin VRV K - 2.18 Outdoor Unit: Abnormal Discharge Pipe Temperature

Daikin VRV K
170 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting Si-95
84 Troubleshooting Inverter K Series
2.8 Indoor Unit: Malfunction of Capacity Determination Device
Remote controller
display
AA
AA
JJ
JJ
Supposed Causes You have forgotten to install the capacity setting adaptor.
Defect of indoor unit PC board
Troubleshooting
(VF035)
Install a capacity setting adaptor.
Replace the indoor unit PC board.
NO
NO
YES
YES
Replace the indoor unit PC board.
The indoor
unit PC board was replaced
with a replacement
PC board.
The indoor
unit is a model that
requires installation of a
capacity setting adaptor when
replacing the PC
board.
SI-95.BOOK Page 84 Friday, March 31, 2000 10:59 AM