Si-95 Troubleshooting
Troubleshooting Inverter K Series 101
2.25 Outdoor Unit: Malfunction of Oil Temperature Thermistor (R5T)
Remote Controller
Display
JJ
JJ
HH
HH
Supposed Causes Defect of oil temperature thermistor (R5T)
Defect of outdoor unit PC board (A1P)
Troubleshooting
(VF051)
Is the connector
is connected to X13A of
the outdoor PC board
(A1P)?
Resistance
is normal when
measured with thermistor
(R5T) disconnected from the
outdoor unit PC board.
(0.6 k~360 k)
Connect the thermistor and and turn on
again.
Replace thermistor (R5T).
Replace outdoor unit PC board (A1P).
YES
YES
NO
NO