EasyManuals Logo
Home>Danfoss>Controller>AK-CC55 Multi Coil

Danfoss AK-CC55 Multi Coil User Manual

Danfoss AK-CC55 Multi Coil
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
1.
2.
3.
y
x
A
350
300
250
200
150
100
50
0
-40 -20 0 20 40 60 80
Danfoss
80G8338
x
y
A
Temp [°C]
R [kohm]
Sensor point (-30 °C, 180 kΩ)
1.
2.
3.
The three sensor points must be:
Lowest temperature in wanted measuring range
Highest temperature value in wanted temperature range
Temp. value in the middle where a high measuring accuracy is required
A sensor error is detected at temperature values below/above the min./max. temperature values typed in for the
sensor points.
Figure 11: Example of sensor points from a NTC sensor
Limitations:
A user dened temperature sensor can only be be dened within the temperature range from -40 – +60 °C and
within the resistance range from 400 – 179.999 ohm.
When applying a new user dened sensor type, please contact Danfoss for validation of compliance and measuring
accuracy.
Appliance cleaning
This function makes it easy for the shops sta to carry out a cleaning of the appliance according to a standard
procedure. Appliance cleaning is activated via a pulse signal – as a rule via a key switch placed on the appliance or
via the AK-CC55 Connect mobile app.
Appliance cleaning is carried out via three phases:
At the rst activation, the refrigeration is stopped, but the fans keep on operating in order to defrost the
evaporators. ”Fan” is shown on the display.
At the second activation, the fans are also stopped and the appliance can now be cleaned. ”OFF” is shown on the
display.
At the third activation, refrigeration is recommenced. The display will show the actual appliance temperature,
o97 setting.
When appliance cleaning is activated, a cleaning alarm is transmitted to the normal alarm recipient. A later
processing of these alarms will document that the appliance has been cleaned as often as planned.
There are no temperature alarms during appliance cleaning.
AK-CC55 Multi Coil
© Danfoss | Climate Solutions | 2022.08 BC365022028193en-000201 | 12

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-CC55 Multi Coil and is the answer not in the manual?

Danfoss AK-CC55 Multi Coil Specifications

General IconGeneral
BrandDanfoss
ModelAK-CC55 Multi Coil
CategoryController
LanguageEnglish

Related product manuals