Control stopped -
Priority
Select the priority of the alarms associated to the
alarm group. Be aware - by selecting "Disable" the
alarms will not be shown on the display or be routed
to the alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
Leak detection - Pri-
ority
Select the priority of the alarms associated to the
alarm group. Be aware - by selecting "Disable" the
alarms will not be shown on the display or be routed
to the alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
Humidity ctrl. - Pri-
ority
Select the priority of the alarms associated to the
alarm group. Be aware - by selecting "Disable" the
alarms will not be shown on the display or be routed
to the alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
Miscellaneous
Table 40: Miscellaneous → Access codes
Access code for local display
Access code for local display
Access code for local display
Table 41: Miscellaneous → Network
Quality of the network communication
Network address of the controller
Communication speed of network
1=Auto, 2=9600 Baud, 3=19200 Baud, 4=38400 Baud
Select parity and stop bit of Modbus messages
Table 42: Miscellaneous → Sensor adjustment
S2 Gas outlet A - Ad-
justment
Correction of sensor signal e.g. due to long sensor ca-
ble
S4 Air OFF evap. A -
Adjustment
Correction of sensor signal e.g. due to long sensor ca-
ble
S4 Air OFF evap. B -
Adjustment
Correction of sensor signal e.g. due to long sensor ca-
ble
S4 Air OFF evap. C -
Adjustment
Correction of sensor signal e.g. due to long sensor ca-
ble
S5 Evaporator A -
Adjustment
Correction of sensor signal e.g. due to long sensor ca-
ble
Table 43: Miscellaneous → Factory reset
With this command you save the controller’s actual
settings as a new basic setting (the earlier factory set-
tings are overwritten).
Reset to factory set-
tings
Command which will revert all controller settings to
factory values.
Advanced
Table 44: Advanced → Advanced injection control
Select how to control the superheat of the evapora-
tor. At adaptive control the superheat reference is
adapted automatically to give the best utilization of
the evaporator surface. At load based control the su-
perheat reference is increased at high loads
Minimum superheat limit where the valve is closing
Superheat close liq-
uid ctrl. A
Minimum limit of superheat where the valve is clos-
ing during adaptive liquid control
Min limit for
amplication factor of the PI controller
adjusting the valve opening degree (expert setting)
Max limit for
amplication factor of the PI controller
adjusting the valve opening degree (expert setting)
Integration time of the PI controller adjusting the
valve opening degree (expert setting)
© Danfoss | Climate Solutions | 2022.08 BC365022028193en-000201 | 55
AK-CC55 Multi Coil