Humidity control
Table 29: Humidity control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
Actual status of output function
Actual status of output function
Select the type of humidity control
0=None, 1=Humidier, 2=Dehumidier
Set-point for the humidity control.
At humidier control, the humidier is started when
the humidity has dropped to the set-point.
At dehumidier control, the dehumidier is stopped,
when the humidity has dropped to the set-point
Dierential for humidity control.
At humidier control, the humidier is stopped when
the humidity has increased with the set dierential
above the set-point.
At dehumidier control, the dehumidier is started,
when the humidity has increased with the set dier-
ential above the set-point
High alarm limit for relative humidity
Low alarm limit for relative humidity
Delay of high and low humidity alarms
Humidity sensor -
Min signal
Humidity sensor -
Max signal
Humidity ctrl. at de-
frost
Select how to control humidity during defrost:
No: Humidity control is stopped during defrost
Yes: Normal humidity control is running during de-
frost
Maximum limit for thermostat air temperature in or-
der for humidity control to run (frost limit)
Minimum limit for thermostat air temperature in or-
der for humidity control to run (frost limit)