Thermostat control
Table 27: Thermostat control
Function
Description
Values
Code
Short name
Control state A
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
u00
u00 Ctrl. state
Control state B
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
U74
U74 Ctrl.State B
Control state C
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
U83
U83 Ctrl.State C
Thermostat air
temp. A
Thermostat temperature
u17
u17 Ther. air
Thermostat air
temp. B
Thermostat temperature
U77
U77 Ther. Air B
Thermostat air
temp. C
Thermostat temperature
U86
U86 Ther. Air C
Food temperature A
Readout of food temperature
U72
U72 Food temp.
S4 Air OFF evap. A
Actual sensor value
u16
u16 S4 air temp.
S4 Air OFF evap. B
Actual sensor value
U76
U76 S4 temp B
S4 Air OFF evap. C
Actual sensor value
U85
U85 S4 temp C
Night condition
Status of the day/night operation (night operation:
on/o)
0=OFF, 1=ON
u13
u13 Night Cond.
Thermostat cut-in
temp.
Readout of the actual cut-in value for the thermostat
u90
u90 Cutin temp.
Thermostat cut-out
temp.
Readout of the actual cut-out value for the thermo-
stat
u91
u91 Cutout temp.
Thermostat run time
A
Read the ongoing cut-in time for the thermostat or
the duration of the last completed cut-in
u18
u18 Ther runtime
Thermostat run time
B
Read the ongoing cut-in time for the thermostat or
the duration of the last completed cut-in
U78
U78 TherRuntimeB
Thermostat run time
C
Read the ongoing cut-in time for the thermostat or
the duration of the last completed cut-in
U87
U87 TherRuntimeC
Thermostat band
Readout of which thermostat is used for regulation:
1= Thermostat band 1
2= Thermostat band 2
1=Band 1, 2=Band 2
u86
u86 Ther. band
Air heater
Actual status of output function
0=OFF, 1=ON
u84
u84 Heat relay
Thermostat mode
Here it is dened how the thermostat is to be operat-
ed. Either as an ordinary ON/OFF thermostat or as a
modulating thermostat.When operation is ”modulat-
ing” the valve will limit the ow of refrigerant so that
the temperature variation will be less than for the
ON/OFF thermostat.The thermostat dierential (r01)
must not be set lower than 2K for ”modulating”. In a
decentralised plant you must select the ON/OFF ther-
mostat setting.
1=ON/OFF, 2=Modulating, 3=ON/OFF Common
r14
r14 Therm. mode
Thermostat sensor
Select which sensor to be used for the thermostat
control
1=Ther. air A, 2=Average all, 3=Maximum all
r99
r99 Ther. sensor
Cut-out 1
Setpoint. The thermostat’s cut-out value when the
given thermostat band is in use
r00
r00 Cutout
© Danfoss | Climate Solutions | 2022.08 BC365022028193en-000201 | 43