Fan control
Table 35: Fan control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
Actual status of output function
Pulse operation of fan
0: No pulse operation
1: Pulse operation when the thermostat is cut out
2: Pulse operation when the thermostat is cut out, but
only during night operation
0=No pulsing, 1=Pulsing cut-out, 2=Pulsing cut-out
night
Period time for pulsing of fan
ON time for fan. The ON period is set as a percentage
of the period time
Fan stop temperature The function stops the fans in
an error situation, so that they will not provide power
to the appliance. If the defrost sensor registers a high-
er temperature than the one set here, the fans will be
stopped. There will be re-start at 2 K below the set-
ting. The function is not active during a defrost or
start-up after a defrost.
You can set whether fans should be operational or
stopped if the function "Forced closing" is activated
here.
0: Fans are OFF
1: Fans are ON
2: Fans are OFF and defrost is not permitted
3: Fans are ON and defrost is not permitted
0=OFF, 1=ON, 2=OFF and suppress defrost, 3=ON and
suppress defrost
Fan stop at blinds
closing
When blinds are closing the fans are stopped in the
dened time delay in order to ensure that the blinds
are closed correctly
© Danfoss | Climate Solutions | 2022.08 BC365022028193en-000201 | 51