Defrost
Table 16: Defrost
Function
Values
R-W
Code
1
2
3
4
5
Min.value
Max.value
Fact.value
Defrost method
0=None, 1=Electrical, 4=Air/
Ocycle
1-3
d01
*
*
*
*
*
0
4
1
Defrost stop limit A
1-2
d02
*
*
*
*
*
0.0 °C
50.0 °C
6.0 °C
Defrost start interval
1-2
d03
*
*
*
*
*
0 hours
240 hours
8 hours
Max. defrost time
1-2
d04
*
*
*
*
*
0 min
360 min
45 min
Time staggering power-up
1-2
d05
*
*
*
*
*
0 min
240 min
0 min
Drip o time
1-2
d06
*
*
*
*
*
0 min
60 min
0 min
Fan start delay
1-2
d07
*
*
*
*
*
0 min
60 min
0 min
Fan start temperature
1-2
d08
*
*
*
-60.0 °C
10.0 °C
5.0 °C
Fan control during defrost
0=OFF, 1=ON, 2=OFF at drip,
3=OFF at high temp
1-2
d09
*
*
*
*
*
0
3
1
Defrost stop method
0=Time, 1=S5 sensor, 2=S4 sen-
sor
1-2
d10
*
*
*
*
*
0
2
0
Pump down delay
1-2
d16
*
*
*
*
*
0 min
60 min
0 min
Max. thermostat run time
1-2
d18
*
*
*
*
*
0 hours
240 hours
0 hours
Min. defrost time
1-2
d24
*
*
*
*
*
0 min
d04
0 min
Rail heat during defrost
0=OFF, 1=ON, 2=Normal control
1-2
d27
*
*
*
*
*
0
2
1
Defrost stop limit 2
1-2
d28
*
*
*
*
*
0.0 °C
50.0 °C
6.0 °C
Max. defrost time 2
1-2
d29
*
*
*
*
*
0 min
360 min
45 min
Display delay after defrost
1-2
d40
*
*
*
*
*
5 min
240 min
30 min
Fan stop temperature
1-2
d41
*
*
*
*
*
-20.0 °C
20.0 °C
0.0 °C
Injection control
Table 17: Injection control
Function
Values
R-W
Code
1
2
3
4
5
Min. value
Max. value
Fact. value
Max. superheat limit
1-2
n09
*
*
*
*
*
n10
20.0 °C
12.0 °C
Min. superheat limit
1-2
n10
*
*
*
*
*
2.0 °C
n09
3.0 °C
MOP temperature
1-2
n11
*
*
*
*
*
-60.0 °C
15.0 °C
15.0 °C
AKV Period time
1-2
(1)
n13
*
*
*
*
*
3 s
6 s
6 s
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
Fan control
Table 18: Fan control
Function
Values
R-W
Code
1
2
3
4
5
Min. value
Max. value
Fact. value
Fan stop high S5 temp.
1-2
F04
*
*
*
-60.0 °C
50.0 °C
50.0 °C
Fan pulsing mode
0=No pulsing, 1=Pulsing cut-
out, 2=Pulsing cut-out night
1-2
F05
*
*
*
*
*
0
2
0
Fan period time
1-2
F06
*
*
*
*
*
1 min
30 min
5 min
Fan ON cycle
1-2
F07
*
*
*
*
*
0 %
100 %
100%
Defrost schedule
Table 19: Defrost schedule
Function
Values
R-W
Code
1
2
3
4
5
Min. value
Max. value
Fact. value
Defrost schedule
0=No, 1=Yes
1-2
t00
*
*
*
*
*
0
1
0
Def. start 1 - Hours
1-2
t01
*
*
*
*
*
0 hours
23 hours
0 hour
Def. start 1 - min
1-2
t11
*
*
*
*
*
0 min
59 min
0 min
Def. start 2 - Hours
1-2
t02
*
*
*
*
*
0 hours
23 hours
0 hour
Def. start 2 - min
1-2
t12
*
*
*
*
*
0 min
59 min
0 min
Def. start 3 - Hours
1-2
t03
*
*
*
*
*
0 hours
23 hours
0 hour
Def. start 3 - min
1-2
t13
*
*
*
*
*
0 min
59 min
0 min
Def. start 4 - Hours
1-2
t04
*
*
*
*
*
0 hours
23 hours
0 hour
Def. start 4 - min
1-2
t14
*
*
*
*
*
0 min
59 min
0 min
Def. start 5 - Hours
1-2
t05
*
*
*
*
*
0 hours
23 hours
0 hour
AK-CC55 Multi Coil