Figure 22: Dehumidier control
If the humidity rises above the SP, then dehumidication is started via a DO signal to a dehumidier.
If the humidity drops below the SP – Humidity dierential, then dehumidication is stopped.
Heating function (application 4 only)
The heating function is used to prevent the temperature from becoming too low, e.g. in a cold room, etc. The limit
for when the heating function cuts o is set as an oset value below the current cut-out limit for the refrigeration
thermostat. This ensures that refrigeration and heating do not occur simultaneously. The dierence for the heating
thermostat has the same value as for the refrigeration thermostat. To prevent that the heating thermostat cuts in
during short-term drops in air temperature, a time delay can be set for when to change from refrigeration to
heating.
Figure 23: Heating function
Digital inputs
There are two digital inputs, DI1 and DI2, with dry contact function, and one digital input DI3 with high voltage
signal.
They can be used for the following functions:
Table 5: Function table and DI settings