Control
Table 22: Control
Function
Values
R-W
Code
1
2
3
4
5
Min. value
Max. value
Fact. value
Alarm relay priority
0=Not used, 1=High Priority,
2=Medium priority, 3=All
1-2
P41
*
*
*
*
0
3
1
Fan stop at blinds closing
1-2
P65
*
*
*
*
*
0 s
300 s
0 s
Rail heat PWM - Period time
1-2
P82
*
*
*
*
*
4 s
60 s
10 s
Refrigerant factor K1
1-3
(1)
P83
*
*
*
*
*
-999
999
300
Refrigerant factor K2
1-3
(1)
P84
*
*
*
*
*
-999
999
300
Refrigerant factor K3
1-3
(1)
P85
*
*
*
*
*
-999
999
300
Max superheat liquid ctrl.
1-2
P86
*
*
*
*
*
P87
20.0 °C
3.0 °C
Min superheat liquid ctrl
1-2
P87
*
*
*
*
*
0.0 °C
P86
1.0 °C
Access code 1
1-1
P88
*
*
*
*
*
0
999
0
Display keyboard lock
0=None, 1=Local, 2=Network
1-2
P89
*
*
*
*
*
0
2
0
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
DO cong and manual
Table 23: DO cong and manual
Function
Values
R-W
Code
1
2
3
4
5
Min. value
Max. value
Fact. value
AO1 Conguration
0=None, 1=Rail heat PWM
1-3
(1)
q09
*
*
*
*
*
0
1
0
EEV override A
1-2
(2)
q11
*
*
*
*
*
0 %
100 %
0%
Fan - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q13
*
*
*
*
*
0
1
0
Defrost A - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q14
*
*
*
0
1
0
Rail heat - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q15
*
*
*
0
1
0
Alarm relay - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q16
*
*
*
*
0
1
0
Light - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q17
*
*
*
*
*
0
1
0
Defrost B - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q22
*
*
0
1
0
Air heater - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q23
*
0
1
0
Humidier - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q26
*
0
1
0
Rail heat PWM - override
1-2
(2)
q27
*
*
*
*
*
0 %
100 %
0%
High temperature - Priority
0=Disabled, 3=Low, 2=Medium,
1=High
0-2
q28
*
*
*
*
*
0
3
1
Low temperature - Priority
0=Disabled, 3=Low, 2=Medium,
1=High
1-2
q29
*
*
*
*
*
0
3
1
Sensor errors - Priority
0=Disabled, 3=Low, 2=Medium,
1=High
1-2
q30
*
*
*
*
*
0
3
1
DI alarms - Priority
0=Disabled, 3=Low, 2=Medium,
1=High
1-2
q31
*
*
*
*
*
0
3
2
Defrost - Priority
0=Disabled, 3=Low, 2=Medium,
1=High
1-2
q32
*
*
*
*
*
0
3
3
Miscellaneous - Priority
0=Disabled, 3=Low, 2=Medium,
1=High
1-2
q33
*
*
*
*
*
0
3
2
Injection - Priority
0=Disabled, 3=Low, 2=Medium,
1=High
1-2
q34
*
*
*
*
*
0
3
2
Control stopped - Priority
0=Disabled, 3=Low, 2=Medium,
1=High
1-2
q35
*
*
*
*
*
0
3
3
Leak detection - Priority
0=Disabled, 3=Low, 2=Medium,
1=High
1-2
q36
*
*
*
*
*
0
3
2
Humidity ctrl. - Priority
0=Disabled, 3=Low, 2=Medium,
1=High
1-2
q37
*
0
3
2
Food temp. sensor
1=Ther. air A, 2=Average all,
3=Maximum all
1-2
(1)
q39
*
*
*
*
*
1
3
1
EEV override B
1-2
(2)
q41
*
*
*
*
0 %
100 %
0%
EEV override C
1-2
(2)
q42
*
0 %
100 %
0%
S4 Air OFF evap. B - Adjustment
1-2
q43
*
*
*
*
-10.0 °C
10.0 °C
0.0 °C
S4 Air OFF evap. C - Adjustment
1-2
q44
*
-10.0 °C
10.0 °C
0.0 °C
Dehumidier -override
0=MAN OFF, 1=MAN ON
1-2
(2)
q46
*
0
1
0
© Danfoss | Climate Solutions | 2022.08 BC365022028193en-000201 | 37
AK-CC55 Multi Coil

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-CC55 Multi Coil and is the answer not in the manual?

Danfoss AK-CC55 Multi Coil Specifications

General IconGeneral
BrandDanfoss
ModelAK-CC55 Multi Coil
CategoryController
LanguageEnglish

Related product manuals