EasyManua.ls Logo

Danfoss AK-CC55 Multi Coil - Alarm Limits and Delays

Danfoss AK-CC55 Multi Coil
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function
Description
Values
Code
Short name
Dierential 1
When the temperature is higher than the set cut-out
+ the set dierential, the compressor relay will be cut-
in. It will cut-out again when the temperature comes
down to the set cut-out limit.
r01
r01 Dierential
Cut-out 2
Setpoint. The thermostat’s cut-out value when the
given thermostat band is in use
r21
r21 Cutout 2
Dierential 2
When the temperature is higher than the set cut-out
+ the set dierential, the compressor relay will be cut-
in. It will cut-out again when the temperature comes
down to the set cut-out limit
r93
r93 Di Th2
Max cut-out limit
Setpoint limitation - The controller’s setting range for
the thermostat setpoint may be narrowed down, so
that too high or too low values are not set accidental-
ly - with resulting damages.To avoid a too high set-
ting of the setpoint, the max. allowable reference val-
ue may be lowered
r02
r02 Max cutout
Min cut-out limit
Setpoint limitation - The controller’s setting range for
the thermostat setpoint may be narrowed down, so
that too high or too low values are not set accidental-
ly - with resulting damages.To avoid a too low setting
of the setpoint, the min. allowable reference value
may be increased
r03
r03 Min cutout
Night oset
Night setback value.The thermostat’s reference will be
the setpoint plus this value when the controller
changes over to night operation.
r13
r13 Night oset
Air heater neutral
zone
Heat function. Set the width of the Neutral Zone for
changeover from cooling to heating
r62
r62 Heat NZ
Air heater start de-
lay
Time delay on transition from refrigeration phase to
heating phase (there is no time delay on transition
from heating phase to refrigeration)
r63
r63 HeatStartDel
Melt interval
Melt function. Only for control of MT cases/rooms (-5
to +10°C). The function ensures that the evaporator
will not be blocked by ice crystals. Here you set how
often the function is to stop the refrigeration and
hence transform the ice crystals to water.
r16
r16 MeltInterval
Melt period
Melt period. Here you set how long an ongoing melt
function is to last
r17
r17 Melt period
Alarm limits and delays
Table 28: Alarm limits and delays
Function
Description
Values
Code
Short name
Alarm status
Actual alarm status
0=OFF, 1=ON
x16
--- Sum alarm
Control state A
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip
o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
u00
u00 Ctrl. state
Control state B
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip
o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
U74
U74 Ctrl.State B
Control state C
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 4=Drip
o,
10=Main switch OFF, 11=Thermostat cutout, 12=Frost
protection S4, 13=Not_used, 14=Defrost, 15=Fan de-
lay, 16=Forced closing, 17=Door open, 18=Melt peri-
od, 19=Modulating temp. control, 20=Emergency
control, 23=Adaptive superheat control, 24=Start in-
jection, 25=Manual control, 26=No refrigerant selec-
ted, 29=Case cleaning, 30=Forced cooling, 31=Door
open, 32=Power-up delay, 33=Air heating, 45=Shut
down controller, 48=Adaptive liquid control
U83
U83 Ctrl.State C
Alarm air temp. A
Measured temperature for alarm thermostat
u57
u57 Alarm air
AK-CC55 Multi Coil
© Danfoss | Climate Solutions | 2022.08 BC365022028193en-000201 | 44

Table of Contents

Related product manuals