Measured temperature for alarm thermostat
Measured temperature for alarm thermostat
Readout of actual high alarm limit for the tempera-
ture monitoring
Readout of actual low alarm limit for the temperature
monitoring
Command for resetting all alarms, unless they are still
active
Upper alarm limit. The limit value is set in absolute
value. The limit value will be raised with the night o-
set during night operation.
Lower alarm limit. The limit value is set in absolute
value
Upper alarm limit. The limit value is set in absolute
value. The limit value will be raised with the night o-
set during night operation.
Lower alarm limit. The limit value is set in absolute
value
Alarm delay (short alarm delay on air temperature). If
the upper or the lower alarm limit values are excee-
ded, a timer function will commence. The alarm will
not become active until the set time delay has been
passed. The time delay is set in minutes
Alarm delay at tempeature pull down conditions
(long alarm delay). This time delay is used during
start-up, during defrost and immediately after a de-
frost. There will be a change-over to the normal time
delay when the temperature has dropped below the
set upper alarm limit.
Time delay for door alarm
Start of refrigeration when the door is open. If the
door has been left open, refrigeration will be started
after the set time.
Time delay for digital input alarm
Time delay for digital input alarm