Setting of required stability of S2 gas outlet tempera-
ture before the superheat reference is reduced (Ex-
pert setting)A higher value will allow more instabillity
in S2 signalA lower value will allow less instabillity in
S2 signal
Expert injection setting - contact Danfoss for further
information
Gain factor for feedback of evaporating temperature
signal Te to the PI controller controlling the superheat
(expert setting)
Amplication factor for modulating temperature con-
trol (Expert setting)
Integration time for modulating temperature control
(Expert setting)
Expert injection setting - contact Danfoss for further
information
Expert injection setting - contact Danfoss for further
information
Expert setting - contact Danfoss for further informa-
tion
Expert readout - contact Danfoss for further informa-
tion
Expert setting - contact Danfoss for further informa-
tion
Calculated maximum opening degree of the injection
valve (expert readout)
Readout showing which part of the injection function
that is in control of the valve opening degree
Values must be changed as per below:
0=Adaptive SH control
1=MOP
2=Superheat close
3=MTR
Expert injection setting - contact Danfoss for further
information
Expert readout - contact Danfoss for further informa-
tion
Expert setting - contact Danfoss for further informa-
tion
Expert injection setting - contact Danfoss for further
information
Calculated maximum opening degree of the injection
valve (expert readout)
Readout showing which part of the injection function
that is in control of the valve opening degree
Values must be changed as per below:
0=Adaptive SH control
1=MOP
2=Superheat close
3=MTR
Expert injection setting - contact Danfoss for further
information
Expert readout - contact Danfoss for further informa-
tion
Expert setting - contact Danfoss for further informa-
tion
Expert injection setting - contact Danfoss for further
information
Calculated maximum opening degree of the injection
valve (expert readout)
Readout showing which part of the injection function
that is in control of the valve opening degree
Values must be changed as per below:
0=Adaptive SH control
1=MOP
2=Superheat close
3=MTR
Expert injection setting - contact Danfoss for further
information
AK-CC55 Multi Coil
© Danfoss | Climate Solutions | 2022.08 BC365022028193en-000201 | 56