Function
Description
Values
Code
Short name
Defrost time C
Read the duration of the ongoing defrost or the dura-
tion of the last completed defrost.
U84
U84 Def. Time C
Start defrost
Command for starting a defrost
0=OFF, 1=ON
x09
--- Def. Start
Stop defrost
Command for stopping an ongoing defrost cycle
0=OFF, 1=ON
x10
--- Def. Stop
Defrost method
Select method of defrost
0=None, 1=Electrical, 4=Air/Ocycle
d01
d01 Def. method
Defrost stop meth-
od
Here you dene whether a defrost cycle is to be stop-
ped by time or by a temperature sensor
0=Time, 1=S5 sensor, 2=S4 sensor
d10
d10 DefStopSens.
Defrost stop limit 1
When the selected defrost stop sensor reaches the set
limit, the defrost cycle is terminated
d02
d02 Def.StopTemp
Defrost stop limit 2
Defrost stop temperature limit when thermostat band
2 is in operation.When the selected defrost stop sen-
sor reaches the set limit, the defrost cycle is termina-
ted
d28
d28 DefStopTemp2
Min. defrost time
Minimum duration of a defrost cycle. The defrost cy-
cle will as a minimum run for the set minimum defrost
time once it is started
d24
d24 Min Def Time
Max. defrost time 1
Max duration of a defrost cycle. The setting is also
used as a safety time if the defrost is stopped on tem-
perature. If the selected defrost stop sensor does not
reach the set defrost stop temperature limit within
the set time, the defrost will be stopped anyway.
d04
d04 Max Def.time
Max. defrost time 2
Max duration of a defrost cycle when thermostat
band 2 is in operation. The setting is also used as a
safety time if the defrost is stopped on temperature. If
the selected defrost stop sensor does not reach the
set defrost stop temperature limit within the set time,
the defrost will be stopped anyway.
d29
d29 MaxDefTime2
Defrost start interval
The function is zeroset and will start the timer func-
tion at each defrost start. When the time has expired
the function will start a defrost. The function is used
as a simple defrost start, or it may be used as a safe-
guard if the normal signal fails to appear. If master/
slave defrost without clock function or without data
communication is used, the interval time will be used
as max. time between defrosts. If a defrost start via
data communcation does not take place, the interval
time will be used as max. time between de-
frosts.When there is defrost with clock function or da-
ta communication, the interval time must be set for a
somewhat longer period of time than the planned
one. In connection with power failure the interval
time will be maintained, and when the power returns
the interval time will continue from the maintained
value. he interval time is not active when set to 0
d03
d03 Def.Interval
Time staggering
power-up
Time staggering for defrost cut-ins during start-up
The function is only relevant if you have several refrig-
eration appliances or groups where you want the de-
frost to be staggered in relation to one another. The
function is furthermore only relevant if you have
chosen defrost with interval start. The function delays
the interval time by the set number of minutes, but it
only does it once, and this at the very rst defrost tak-
ing place when voltage is connected to the controller.
The function will be active after each and every pow-
er failure.
d05
d05 Time stagg.
Max. thermostat run
time
Defrost on demand. Aggregate refrigeration time set
here is the refrigeration time allowed without de-
frosts. If the time is passed, a defrost will be started.
With setting = 0 the function is not in use.
d18
d18 MaxTherRunT.
Pump down delay
Set the time where the evaporator is emptied of re-
frigerant prior to the actual defrost cycle
d16
d16 Pump dwn del
Drip o time
Here you set the time that is to elapse from a defrost
and until the compressor is to start again. (The time
when water drips o the evaporator).
d06
d06 DripO time
Max. hold time
Max. standby time after coordinated defrost. When a
controller has completed a defrost it will wait for a
signal tellingthat the refrigeration may be resumed. If
this signal fails to appear for one reason or another,
the controller itself will start the refrigeration when
the standby time has elapsed.
o16
o16 MaxHoldTime
© Danfoss | Climate Solutions | 2022.08 BC365022028193en-000201 | 49
AK-CC55 Multi Coil

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-CC55 Multi Coil and is the answer not in the manual?

Danfoss AK-CC55 Multi Coil Specifications

General IconGeneral
BrandDanfoss
ModelAK-CC55 Multi Coil
CategoryController
LanguageEnglish

Related product manuals