DHP-AL, connection diagram VLD
General connection diagram DHP-AL, system VLD.Figure 49: 
Position  Name
1   Heat pump (part of the delivery)
2   Supply line
3   Return line
4   Safety valve
5   Expansion tank
6   Strainer (part of the delivery)
7   Flexible hoses (part of the delivery)
8   -
9   Mixer valve
10  Exchange valve
11  Safety valve (9 bar) (included in delivery)
12  Vacuum valve
13  Non-return valve
14  Shut-off valve
15  Cold water
16  Hot water
17  Water heater (part of the delivery)
18  Bleed valve at stainless steel water heater
19  External auxiliary heater
20  Circulation pump
21  Non-return valve
22  Moved supply line sensor (included in heat pump)
23  Auxiliary shunt
24  Safety valve for temperature and pressure (mounted only on cer-
tain models, see chapter 6)
6.4  Safety valves
⚠
Radiator systems with a closed expansion tank must also be 
equipped with an approved pressure gauge and safety valve, 
minimum DN 20, for a maximum 1.5 bar opening pressure, or 
according to country specific requirements.
⚠
Cold and hot water pipes as well as overflow pipes from 
safety valves must be made of heat resistant and corrosion-
resistant material, e.g. copper. The safety valve overflow pipes 
must have an open connection to the drain and visibly flow 
into this in a frost-free environment.
⚠
The connecting pipe between the expansion tank and the 
safety valve must slope continuously upwards. A continuous 
upwards slope means that the pipe must not slope down-
wards from the horizontal at any point.
6.5  Connecting cold and hot water pipes
1.  Connect the cold water and hot water pipes with all the neces-
sary components according to the connection diagram for the 
relevant system. 
6.6  Connecting the heating system supply 
and return lines
All pipes should be routed in such a way that vibrations cannot be 
transmitted from the heat pump through the piping and out into 
the building. This also applies to the expansion pipe. To avoid the 
transmission of vibrations, we recommend that flexible hoses are 
used for the supply line and return line on both the heating system 
and brine system sides. Flexible hoses are available to purchase 
from Danfoss AS. The figures below show how appropriate and 
inappropriate installations look using this type of hose.
To avoid noise caused by pipe mounting, rubber-coated clamps should 
be used to prevent the transmission of vibrations. However, installation 
should not be too rigid and the clamps must not be too tight.
Do not twist the flexible hoses as they are installed. At    Figure 50: 
    threaded connections, use a counterhold spanner.
Cut the hose to the correct length to avoid excess    Figure 51: 
    bowingout or stretching at bends.
Cut the hose to the correct length to avoid excess bowing-   Figure 52: 
    out or stretching and offset the ends so that the hose is not  
    installed completely straight.
Use fixed pipe bends to avoid excess stress on bends next to  Figure 53: 
    connections.
1.  Connect the supply line with a flexible hose connection and 
with all the necessary components.
2.  Connect the return line with a flexible hose connection and 
with all the necessary components including a filter.
3.  Insulate the supply and return lines.
4.  Connect the expansion tank to the expansion outlet (22mm Cu) 
on the top of the heat pump.