Cause Troubleshooting Remedy
12. Overfilled refrigerant circuit.  Using manometer apparatus and thermometer, 
check that the unit’s overheating is correct for 
the specific refrigerant. 
Follow the correct procedure (depend-
ing on type of refrigerant) to add the 
correct amount of refrigerant.
If there appears to be a leak in the refrig-
erant circuit, carry out leak tracing and 
any necessary corrective action. 
13. Blocked condenser on the water side.  If there is no strainer in the heating system, 
there is a risk of dirt sticking in the condenser 
and blocking it. Unfortunately there is no easy 
way of checking if the condenser is blocked.
You can carry out a test by allowing the com-
pressor and circulation pumps to remain in 
operation and after a while, check that the 
delivery pipe becomes hot and that the circula-
tion pumps work (for circ.pumps with a venting 
screw, unscrew it and feel if the pump rotor 
rotates using a screwdriver).
Then read the temperature on both connection 
pipes to the condenser: 
If the temperature difference is <3°C, the con-
denser is probably blocked.
If the temperature difference is 3-13°C, it is 
probably not blocked.
If the temperature difference is >13°C, the con-
denser is probably blocked.
If the condenser is thought to be 
blocked, try flushing it. If this does not 
work, it must be replaced 
14. Blocked condenser on the refrigerant 
side. 
Using manometer apparatus and thermometer, 
check that the unit’s overheating is correct for 
the specific refrigerant. 
If the condenser is thought to be 
blocked by oil for example, try blowing 
nitrogen through it to release the oil. 
If this does not work, it must be replaced
Problem – Alarm MS (motor protection)
Cause Troubleshooting Remedy
1. Phase drop or blown fuse.  Check that all phases are present on the termi-
nal block for incoming supply. If not, check the 
fuses in the cabinet. 
Also check that all wiring is secure, if screw 
terminals are used they must be properly tight-
ened, if phoenix flat spring terminals are used, 
the cables must be secure in the correct hole 
with load on the cable.
If any of the phases are not present, check 
backwards towards the building’s main 
electrical cabinet. If there are no phases 
there, contact the network supplier.
2. Defective soft-starter.  Measurement check and establish that when 
the control computer gives a signal (there must 
be voltage between A1 & A2 on the soft-start-
er), the soft-starter releases all three phases 
down to the compressor. 
If the soft-starter does not release the 
phases when it receives signals from the 
control computer, replace it.
3. Defective contactor.  Measurement check and establish that when 
the control computer gives a signal (there must 
be voltage between A1 & A2 on the contactor), 
the contactor releases all three phases down to 
the compressor. 
If the contactor does not release the 
phases when it receives signals from the 
control computer, replace it.
4. Defective or incorrectly set motor protec-
tion. 
Use a hook-on meter to establish when the 
motor protection deploys, check what the 
motor protection is set to. Compare with the 
table.
If the motor protection is defective, 
replace it.
If incorrectly set, adjust to the correct 
value.
5. Cable break.  Check the supply to the motor protection//
soft-starter/compressor.
If a cable is damaged, replace it.