9  Installing accessories/additional 
functions
9.1  Room temperature sensor
The room temperature sensor has a temperature sensor that 
provides a further value that the control computer can use when 
calculating the supply temperature. The influence of the room sen-
sor in the calculation can be set in the menu HEAT CURVE-> ROOM 
FACTOR. Default setting for ROOM FACTOR is 2 but can be adjusted 
from 0 (no impact) to 4 (large impact).
The difference between the desired and actual indoor temperature 
is multiplied by the set value for ROOM FACTOR. The set point on 
the heating system’s supply line increases or decreases with the 
result depending on whether there is a deficit or surplus of heat. 
The table below shows examples of how the set point for the sup-
ply line is affected at CURVE 40 with different settings for ROOM 
FACTOR. 
In the event of a heating deficit:
ROOM 
FACTOR
Desired room 
temperature, °C
Actual room 
temperature, °C
Set point for 
supply line, °C
0 22 20 40
1 22 20 42
2 22 20 44
3 22 20 46
4 22 20 48
In the event of a surplus of heat the conditions are the opposite:
ROOM 
FACTOR
Desired room 
temperature, °C
Actual room 
temperature, °C
Set point for 
supply line, °C
0 20 22 40
1 20 22 38
2 20 22 36
3 20 22 34
4 20 22 32
⚠
NOTE! The room temperature sensor is connected to a safety 
extra-low voltage. 
1.  Install the room temperature sensor in a location in the house 
where the room temperature is relatively constant: 
• Centrallylocatedinthehouse
• Ateyelevel
• Notindirectsunlight
• Notinadraft
• Notinaroomwithalternativeheating
2.  Hang a thermometer next to the room temperature sensor in 
order to calibrate it after connecting it.
3.  Connect the room temperature sensor to terminal blocks 303 
and 304.
4.  After connecting the room temperature sensor, it is calibrated 
by holding in both buttons for 15 seconds until the display 
starts to flash.
5.  Set the actual room temperature that the thermometer shows. 
6.  Wait 10 seconds until the display stops flashing.
If the display shows “--” for outdoor temperature no outdoor tem-
perature has been read.
9.2  EVU function
The EVU function prevents the operation of HEATPUMP, ADD.HEAT 
and CIRC.PUMP as long as the contact is closed. The text EVU STOP 
is shown in the display when this function is active.
• TheEVUfunctionisactivatedbymakingaconnectionbetween
terminal blocks 307 and 308 using an external 1-pin timer. 
9.3  Tariff control
The room temperature lowering function provides a regular, tem-
porary lowering of the indoor temperature. 
• Thetariffcontrolisactivatedbymakingaconnectionbetween
terminal blocks 307 and 308 using an external 1-pin timer and a 
10 kohm resistor. 
• Theextenttowhichthetemperatureisloweredissetinthe
menu INFORMATION -> Heatcurve -> REDUCTION.
9.4  Flow switch/level switch
In certain countries there is a requirement that the heat pump must 
be equipped with a level switch for the brine system. Always check 
local rules and regulations before commissioning the heat pump.
Level switch in the expansion tank/bleed tank.Figure 74: 
Position  Name
1    Safety valve
2    Level switch
3    Floats
• Connecttheflowswitchorlevelswitchtoterminalblocks217
and 219.
9.5  Higher hot water temperature
⚠
Does not apply to models with refrigerant R134a, models 
DHP-C -4H, -5H and -7H. 
⚠
NOTE! Never connect the heat pump to provide a higher 
temperature unless the heating or hot water systems require 
it. Higher temperatures increase the load on the heat pump.
If necessary, the heat pump can be connected to produce hot-
ter water for the heating system and hot water system when it is 
installed.
The pressure switches on the compressor’s pressure pipe.Figure 75: 
1.  Move the grey cables, which are normally connected to pres-
sure switch A, to pressure switch B.