Cause Troubleshooting Remedy
9. Insufficient exchange surface to transfer 
the heat pump’s output to the heater.
(Only applies to heat pumps with a separate 
heater)
Is the exchange surface too small?
Can the heater cope with the heat pump’s 
output?
Replace with a heater with a larger 
exchange surface.
10. Heat loss in the hot water pipe.  Open the hot water tap, read off the tem-
perature on the outgoing hot water pipe 
from the heat pump and the temperature of 
the hot water. The temperature difference 
measured between the heat pump and hot 
water indicates the temperature loss.
Examples of temperature loss causes:
•Longwaterpipes.
•Uninsulatedhotwaterpipes.
•Hotwaterpipesroutedthroughcoldareas.
Other causes that can affect the hot water 
temperature:
•Isamixervalveinstalledinthesystem?
Temperature set too low on the mixer 
valve? Leaking mixer valve?
•Watertapfault?Leakingthermostatmixer?
If any problems occur during troubleshoot-
ing as per the points, carry out corrective 
actions.
To quickly check that the heat pump’s hot 
water production works as it should, drain 
the hot water so that the heat pump starts 
to produce the hot water. When done, read 
off the temperature on the top sensor and 
on the start sensor. The top sensor should 
show a temperature of around 50-55°C and 
the start sensor around 45-48°C. If, after 
completed hot water production, these 
temperatures are obtained, this means that 
you have the correct temperature and vol-
ume of hot water in the water heater.
HEATING COMFORT
Problem – Too cold
Cause Troubleshooting Remedy
1. The heat pump’s control computer is 
not set/adjusted to the customer’s require-
ments/wishes. 
Check the ROOM and CURVE and MAX set-
tings.
Adjust incorrect values in the heat pump’s 
control computer.
ROOM = Desired indoor temperature
CURVE = Should be set so that the desired 
indoor temperature (ROOM) is maintained 
regardless of the outdoor temperature.
MAX = Highest set-point value on the sup-
ply line regardless of the outdoor tempera-
ture.
2. Incorrect operating mode set in the heat 
pump’s control computer. 
Check which operating mode is set. If the incorrect operating mode is set, 
change to the desired operating mode.
3. Sensor fault, OUTDOOR/ROOM/Supply 
line/Return line. 
Check what the relevant sensor shows, is it 
a plausible/actual value?
Measure the resistance of the sensor, check 
against the ohm table in the Measurement 
points section.
If the sensor is defective, replace it.
4. The 3-way valve has jammed in hot water 
mode. 
1. Check the function of the 3-way valve 
motor by test running it manually. If the 
motor does not shift mode during manual 
test operation, check that there is voltage to 
the motor, see wiring diagram.
2. Detach the motor and test closing and 
opening of the valve by pressing the con-
trol arm.
1. Is the motor being supplied with voltage 
according to the wiring diagram in both 
operating instances? 
MANUAL TEST – VXV HOT WATER  
0=Radiator mode, arm out from valve. 
1=Hot water mode, arm positioned towards 
the valve. 
If there is voltage to the motor but the arm 
does not shift mode, replace it.
2. Take out and clean the jammed insert, or 
replace with a new insert.
5. Defective electric heating element.  Use a buzzer and check if all coils in the 
electric heating element are intact.
If the electric heating element is defective, 
replace it.