Problem ā Runs on electric heating element
Cause Troubleshooting Remedy
1. Operating mode ADD.HEAT is selected.  If this operating mode is selected, the aux-
iliary heater is used for heating and hot 
water production, not the compressor.
If ADD.HEAT mode is selected and you no 
longer want it, change to AUTO, the heat 
pump then controls both the compressor 
and auxiliary heater.
2. The compressor cannot run due to an 
alarm. 
Check the alarm that is indicated in the 
display.
Rectify the problem and rest the alarm. See 
the Operational problem ā Alarm, section.
3. The integral value has reached the start 
level for the auxiliary heater. 
Check what the integral value is in the con-
trol computer.
If the auxiliary heater is in operation 
because the integral value has counted 
down to the start value, the computer 
reacts as it should, see the Heat pump for 
further information.
4. Peak heat operation (legionella function) 
is running. 
Check if the heat pump runs peak heat. See 
the instructions for the relevant model. 
Peak heat operation occurs in connection 
with hot water production with the set 
interval. The compressor should then start 
to produce hot water and 2 minutes later 
the auxiliary heater starts, the compressor 
should then stop and the stop temperature 
is reached with only the auxiliary heater 
connected. Take no corrective action.
5. The heat pump has stopped on HIGH 
RETURN. 
ā¢īCheckīwhatītheīMAXīRETURNīvalueīisīsetī
at in the heat pumpās control computer. It 
must be adjusted to the unitās maximum 
supply temperature and the systemās delta 
temperature so that it does not cut at too 
high a return temperature when the highest 
supply temperature is transmitted.
ā¢īCheckīwhatītheīreturnīlineīsensorīshows,ī
is it a plausible/actual value? If not, take 
a resistance reading from the sensors 
and check against the ohm table in the 
Measurement points section.
If the MAX RETURN value is not adjusted for 
the system according to the troubleshoot-
ing window, adjust it.
If the sensor is defective, replace it.
6. The compressor runs backwards. The 
incoming phases have the incorrect 
sequence (only applies to 3-phase heat 
pumps).
If the compressor runs backwards, it will 
not cope with compressing the refrigerant 
and therefore does not produce the correct 
power, which leads to the control computer 
requesting auxiliary heating. 
ā¢īIfītheītextīERRīPHASEīSEQīappearsīinītheī
display when the heat pump is powered, 
(only appears in the first 10 minutes) this 
means that the phases have the incorrect 
sequence.
ā¢īWhenītheīcompressorīisīrunning,īcheckī
the delivery pipe temperature by feeling 
the delivery pipe that should be hot (not 
just warm) even a little distance from the 
compressor if the phases are correctly 
sequenced.
ā¢īWhenītheīcompressorīrunsīwithītheīphas-
es incorrectly sequenced a strange noise 
may be heard (loud, rattling) when the 
compressor runs backwards.
If the phases are in the incorrect order, 
switch two incoming phases at the main 
terminal block and recheck according to the 
troubleshooting window.
7. Changed conditions. Have you increased 
your heating and/or hot water demand? 
ā¢īIfītheīheatīpumpīhasībeenīdimensionedī
for a certain demand and this demand is 
increased, the heat pump might not be able 
to maintain the desired room temperature.
ā¢īIfīhotīwaterīconsumptionīincreases,īaī
larger proportion of time is used to produce 
hot water, which means less time for heat 
production (only applies to VL-systems).
If the heat pump cannot cope with the 
demand, replace it with one with a higher 
output or supplement it with a higher out-
put auxiliary heater.