Problem – Short operating times despite heating demand
Cause Troubleshooting Remedy
ROOM and/or CURVE set too high in com-
bination with a heating system with poor 
circulation due to closed radiator valves, too 
small elements or insufficient water volume. 
A tight fitting system with poor pipe dimen-
sions may produce the same phenomena. 
Check if the heat pumps starts, if the supply 
temperature rises quickly whilst nothing 
happens to the return temperature.
If this happens and the heat pump is 
stopped by the hysteresis function to later 
drop in temperature (supply) as quickly to 
start again, but cannot due to time condi-
tions in regulation, this means that the heat 
pump cannot transport the heat away from 
the condenser as it should.
In such a case, hysteresis starts and stops 
the heat pump often.
Adjust ROOM and CURVE if necessary, 
ensure that there is sufficient flow over the 
condenser and the heating circuit.
Problem – Connection of external AH
Cause Troubleshooting Remedy
Incorrectly connected auxiliary heater. Does 
not start when the control computer gives 
the signal. 
Check the connection against the instruc-
tions/wiring diagram. Test the function in 
manual mode.
If the auxiliary heater is incorrectly connect-
ed, reconnect according to the instructions.
OUTDOOR UNIT
Problem – Noise/loud noise
Cause Troubleshooting Remedy
1. Positioning the outdoor unit.  Determine whether the outdoor unit can be 
moved to a more suitable location.
When positioning the outdoor unit, its 
direction does not affect its performance. 
The outdoor unit does not need to be posi-
tioned as close to the heat pump as neces-
sary, it can be positioned as far as 30 ”pipe 
metres” way.
2. Connection/wall lead-ins.  Check that the unit is installed according to 
the instructions. 
Is the outdoor unit secured to the wall?
Rigid mountings can generate noise from 
the outdoor section via walls in the house.
Problem – Defrosting problems
Cause Troubleshooting Remedy
1. Location/calibration of the outdoor sen-
sor. 
Check that the outdoor sensor is installed 
according to the installation instructions 
and that it is correctly calibrated.
Install according to the instructions and 
calibrate, if necessary. Alternatively, the 
outdoor sensor can be located behind the 
outdoor unit 20 cm out from the rear side of 
the outdoor unit.
2. Brine temperature in/out.  Measurement check the temperatures with 
a thermometer.
If necessary, calibrate BRINE IN and BRINE 
OUT in the heat pump’s control computer.
3. The defroster shunt does not regulate as 
it should. 
Manually test to check if the defroster 
shunt opens and closes the flow over the 
defroster tank. 
If the motor switches position when test-
ing, but defrosting still does not function, 
remove the motor and try closing and 
opening the valve by hand by pressing in 
the control arm.
If the motor is defective, replace it.
If the insert jams, remove and clean/lubri-
cate it, or replace it.