FC 300 CANopen
MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark 9
How to Install
Cabling
Cable Lengths
Cable Specifications
Bus cabel Bus length in
meters
Resistance
m/m
Cross section
mm²
Termination resistor
Baudrate
Kbit/s
0-40
40-300
300-600
600-1000
70
<60
<40
<26
0.25-0.34
0.34-0.6
0.5-0.6
0.75-0.8
124
150-300
150-300
150-300
1000 (up to 30m)
>500 (up to 100m)
>100 (up to 500m)
>50 (up to 1000m)
Cable Specifications
The cable used should be according to the pecifications.
Be aware that the “Flat Cable” is an unscreened cable type, and is not suited for use with frequency