DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
24
Danfoss Electronics spa
Air Handling seq. - user manual
4.5| Locking sequences
For each coil it is possible to lock the cooling or heating control if the outside temperature measured with the “OUT
– Outside Temp” probe goes beyond the following limits.
LOCKING SEQUENCES
COI Coils Min Max Default U.M. Text value
CL1 Coil 1
b29 Cooling lock -40,0 100,0 -30,0 °C
b30 Heating lock -40,0 100,0 90,0 °C
CL2 Coil 2
b59 Cooling lock -40,0 100,0 -30,0 °C
b60 Heating lock -40,0 100,0 90,0 °C
CL3 Coil 3
b89 Cooling lock -40,0 100,0 -30,0 °C
b90 Heating lock -40,0 100,0 90,0 °C
Tab 17_ [Coils control - Locking sequences]
Fig 11 _ [Coils control - Locking sequences]