If present, the pump is activated when request is sent to the humidier. You can dene the load percentage to
switch on the pump, via PON parameter, and to switch it OFF, via POF parameter.
* Pump switches ON at 5% and
OFF at 0%.
You can also dene a switch OFF delay POd for the pumps.
HUMIDIFICATION PUMPS
PUM Pumps Min Max Default U.M. Text value
STU Setup
POd Pump delay at OFF 0 9999 5 SEC
PON Power request activation 0 9999 5,0 %
POF Power request deactivation 0 9999 0,0 %
Tab 35_ [Humidity control - Humidication pumps]
* Humidication pump is not
activated in case of winter start.
11.3| Dehumidier control
Dehumidication can be performed:
with an outside dehumidier activated by the digital output “DEU
– Dehumidier “and analog output “DHU – Dehumidier”.
Fig 41_ [Humidity control - Dehumidier control]
activating the cooling coil (see “11.3.1] Cooling coil in dehumidication”).
1.