DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
54
Danfoss Electronics spa
Air Handling seq. - user manual
12.3| Fans and antifreeze
In case of water coils and antifreeze alarm, is necessary to stop fans.
Parameter F04, for stopping regulation if FAN is OFF, must be set to NO
Parameter F05, for stopping FAN if antifreeze alarm is ON, must be set to YES
12.4| Fans lock
Is possible to lock/unlock fans through the digital input “LOF-Lock Fan” or through the user interface (see “2.4.5]
Utilities”).