Air Handling seq.- user manual
DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
45
11| Humidity control
Fig 38_ [Humidity control - Humidity control]
HUMIDITY CONTROL SETPOINT
SET Setpoint Min Max Default U.M. Text value
MST Main Setpoint
HUM Min setpoint humidity 0 100,0 40,0 %
DEH Max setpoint humidity 0 100,0 60,0 %
Tab 32_ [Humidity control - Humidity control setpoint]
HUMIDITY CONTROL REGULATION
HCT Humidity Control Min Max Default U.M. Text value
REG Regulation
U01 Control probe 1 3 RHU ;NO;SHU;RHU
U02 Humidication proportional
band
0 20,0 5,0 %
U03 Humidication integral time 0 9999 0 SEC
U04 Humidication derivative
time
0 9999 0 SEC
U05 Dehumidication prop.
band
0 20,0 5,0 %
U06 Dehumidication integral
time
0 9999 0 SEC
U07 Dehumidication derivative
time
0 9999 0 SEC
Tab 33_ [Humidity control - Humidity control regulation]