0-41 [O] Key on LCP
Option: Function:
[0] Disabled Key disabled avoids accidental usage of the key.
[1] * Enabled [O] key is enabled.
[2] Password
Avoid unauthorised stop. If parameter 0-41 [O]
Key on LCP is included in My Personal Menu,
dene the password in parameter 0-65 Personal
Menu Password. Otherwise, dene the password
in parameter 0-60 Main Menu Password.
0-42 [Auto on] Key on LCP
Option: Function:
[0] Disabled Key disabled avoids accidental usage of the
[Auto On] key.
[1] * Enabled [Auto On] key is enabled.
[2] Password
Avoid unauthorised start in Auto mode. If
parameter 0-42 [Auto on] Key on LCP is included
in My Personal Menu, dene the password in
parameter 0-65 Personal Menu Password.
Otherwise, dene the password in
parameter 0-60 Main Menu Password.
0-43 [Reset] Key on LCP
Option: Function:
[0] Disabled Key disabled avoids accidental usage of the
[Reset] key.
[1] * Enabled [Reset] key is enabled.
[2] Password
Avoid unauthorised resetting. If
parameter 0-43 [Reset] Key on LCP is included
in parameter 0-25 My Personal Menu, dene
the password in parameter 0-65 Personal
Menu Password. Otherwise, dene the
password in parameter 0-60 Main Menu
Password.
[3] Enabled
without OFF
[4] Password
without OFF
[5] Enabled with
OFF
Pressing the key resets the frequency
converter, but does not start it.
[6] Password
with OFF
Prevents unauthorised reset. Upon
authorised reset, the frequency converter
does not start. See option [2] Password for
information on how to set the password.
3.2.6 0-5* Copy/Save
Copy parameters from and to the LCP. Use these
parameters for saving and copying set-ups from 1
frequency converter to another.
0-50 LCP Copy
Option: Function:
[0] * No copy No function.
[1] All to LCP Copies all parameters in all set-ups from the
frequency converter memory to the LCP
memory. For service purposes it is
recommended to copy all parameters to the
LCP after commissioning.
[2] All from LCP Copies all parameters in all set-ups from the
LCP memory to the frequency converter
memory.
[3] Size indep.
from LCP
Copies only the parameters that are
independent of the motor size. The latest
selection can be used to programme several
frequency converters with the same function
without disturbing motor data which are
already set.
[10] Delete LCP
copy data
0-51 Set-up Copy
Option: Function:
[0]
*
No copy No function.
[1] Copy to
set-up 1
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up) to set-up 1.
[2] Copy to
set-up 2
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up) to set-up 2.
[3] Copy to
set-up 3
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up) to set-up 3.
[4] Copy to
set-up 4
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up) to set-up 4.
[9] Copy to
all
Copies the parameters in the present set-up to
each of the set-ups 1 to 4.
3.2.7 0-6* Password
0-60 Main Menu Password
Range: Function:
100* [-9999 -
9999 ]
Dene the password for access to the Main
Menu via the [Main Menu] key. If
parameter 0-61 Access to Main Menu w/o
Password is set to [0] Full access, this
parameter is ignored.