Appendix C
C.1 Pressure Regulating Valve Installation Instructions
When installing the KVP 22, certain steps must be performed to ensure no internal valve damage occurs.
1. Remove the KVP 22 adjustment cap as shown in Figure C-1 Adjustment Cap Lift.
Figure C-1 Adjustment Cap Lift
2. Use an appropriately sized hex wrench to turn the setting screw. Turn three (3) complete revolutions
counterclockwise.
Figure C-2 Hex Wrench
3. Remove the Schrader valve cap and then the Schrader valve.
Figure C-3 Schrader Valve Removal
4. Clean all connections with a sanding cloth and then apply soldering flux to the exterior of the clean
copper tube. Do the same to the mating copper pipe that will connect to the valve.