4.3 Compressor I/O Board Mounting Details
The Compressor I/O Board ( Figure 4-4 Compressor I/O Board) must be installed in a Underwriters Laboratories (UL)
approved electrical enclosure equipped with DIN EN 50022, 50035, or 50045 mounting rails. The board should be
mounted in a dry area, free from vibration and electrical noise.
NOTE
The UL listed enclosure should protect against moisture and other corrosive elements.
Figure 4-4 Compressor I/O Board
4.3.1 Compressor I/O Board Mounting Instructions
1. Tilt the I/O Board as shown in Figure 4-5 Compressor I/O Board Installation in order to engage it into
the DIN Rail.
2. Lower the I/O Board until it snaps into place.
Figure 4-5 Compressor I/O Board Installation